Industrial Projects & Case Studies

Explore documented engineering write-ups detailing the problem encountered, our technical solution, the operational result, and complete hardware specifications.

Interactive Controls Modernization

Before & After: Machine Controls Retrofit

See how upgrading obsolete relay logic into an organized Siemens PLC control enclosure eliminates unmapped wiring and stops recurring production downtime.

Modernized Siemens PLC control panel with clean wire ducting and safety relays
AFTER: MODERN SIEMENS S7-1500 PLC
Obsolete relay logic cabinet with tangled point-to-point wiring
BEFORE: OBSOLETE RELAY LOGIC
0% (OLD RELAY)100% (NEW PLC)
FAULT ISOLATION
< 3 MINUTES
Plain text HMI alarms
SPARE AVAILABILITY
CURRENT OEM
Siemens / Rockwell stock
RECIPE CHANGEOVER
INSTANT
HMI stored recipes
SAFETY INTEGRATION
DUAL CHANNEL
Monitored E-stop loops
// Project Case Studies

Field Write-ups & Engineering Specs

High-Speed Packaging Line Siemens S7-1500 Retrofit
Food & Beverage Processing
Cincinnati, OH Area

High-Speed Packaging Line Siemens S7-1500 Retrofit

[Problem]

A regional packaging plant was operating a high-speed cartoning line controlled by an obsolete, discontinued PLC. Replacement cards were unavailable, and an intermittent communication error caused multi-hour shutdowns three times per week.

[What We Did]

Engineered a complete control retrofit built around a Siemens S7-1500 PLC and SIMATIC Comfort HMI inside TIA Portal. Pre-built and tested the control panel in-house, mapped all field I/O, rewrote the machine sequence logic with structured fault diagnostics, and commissioned the line over a weekend shutdown.

[Result]

The packaging line restarted on schedule Monday morning with zero startup delay. Unplanned electrical stops dropped to zero, and the new touchscreen HMI gives maintenance clear plain-text descriptions for any sensor blockage.

// ENGINEERING SPECIFICATIONS:
PLC: Siemens S7-1500 (TIA Portal)
HMI: Siemens SIMATIC 12" Comfort Panel
DRIVE: Siemens SINAMICS VFDs over Profinet
VOLTAGE: 480V 3-Phase / 24VDC Control
Documented Project Case StudyRequest Similar System
480V Motor Control Center & Automatic Power Factor Correction
Plastics & Heavy Manufacturing
Southwestern Ohio

480V Motor Control Center & Automatic Power Factor Correction

[Problem]

A plastics facility operating 14 extruder lines was incurring thousands of dollars in monthly utility penalty fees due to a poor power factor of 0.74, accompanied by frequent thermal tripping in their aging motor control center.

[What We Did]

Conducted on-site harmonic and power quality measurements, designed and fabricated a custom 300 kVAR automatic capacitor bank panel with detuned reactors to prevent resonance, and rebuilt the main MCC distribution feeds with balanced phase loading.

[Result]

Plant power factor improved from 0.74 to 0.96, eliminating utility surcharges completely. Main panel operating temperatures dropped by 18°F, preventing nuisance thermal breaker trips.

// ENGINEERING SPECIFICATIONS:
PLC: Microprocessor Power Factor Controller
HMI: Digital Power Quality Multi-Meter
DRIVE: Detuned Iron-Core Reactor Banks
VOLTAGE: 480V 3-Phase 60Hz
Documented Project Case StudyRequest Similar System
Multi-Axis Servo Positioning & Drive Synchronization
Plastics & Packaging
Northern Kentucky

Multi-Axis Servo Positioning & Drive Synchronization

[Problem]

An automated pick-and-place indexing machine suffered constant mechanical drift due to worn mechanical cam linkages, producing scrap rates of up to 4.5% and requiring daily manual recalibration.

[What We Did]

Replaced the mechanical cam system with a synchronized dual-axis AC brushless servo drive system with absolute multi-turn encoders. Integrated coordinated motion profiles and homing routines directly into the machine automation controller.

[Result]

Scrap rates dropped to under 0.2%, mechanical vibration was eliminated, and product changeover time was reduced from 45 minutes of mechanical adjustments to a 10-second recipe selection on the HMI.

// ENGINEERING SPECIFICATIONS:
PLC: Delta Industrial Motion Controller
HMI: Delta 10" Widescreen Color Touchscreen
DRIVE: Delta AC Servo Drives & Brushless Motors
VOLTAGE: 230V 3-Phase System
Documented Project Case StudyRequest Similar System
FANUC Robotic Workcell Electrical Diagnostics & Safety Upgrade
Manufacturing & Machine Shops
Cincinnati, OH Area

FANUC Robotic Workcell Electrical Diagnostics & Safety Upgrade

[Problem]

A production welding and handling cell utilizing a FANUC robot was experiencing intermittent emergency stop lockouts. Floor technicians could not isolate whether the fault originated in the robot controller, safety gate interlocks, or PLC handshake.

[What We Did]

Diagnosed the intermittent safety loop failure down to a chatter in an aging mechanical door interlock switch. Replaced mechanical switches with dual-channel monitored safety switches, rewired the E-stop safety circuit to current standards, and reprogrammed the robot-to-PLC handshake over Industrial Ethernet.

[Result]

Emergency stop lockouts were resolved immediately. Robot safety status and individual gate statuses are now clearly displayed on the cell operator interface for instant troubleshooting.

// ENGINEERING SPECIFICATIONS:
PLC: Allen-Bradley CompactLogix
HMI: PanelPlus Operator Screen
DRIVE: FANUC R-30iB Robot Controller
VOLTAGE: 480V 3-Phase / 24VDC Safety Circuits
Documented Project Case StudyRequest Similar System
Industrial Pumping Station VFD Control Panel Build
Commercial & Logistics Facilities
Greater Cincinnati, OH

Industrial Pumping Station VFD Control Panel Build

[Problem]

Three 50 HP centrifugal chilled water pumps were running direct-on-line (DOL) at full speed continuously, generating massive in-rush current spikes and water hammer shock throughout facility piping.

[What We Did]

Designed and built a custom NEMA 12 three-bay control enclosure featuring three 50 HP Variable Frequency Drives with bypass contactors, pressure transducer PID feedback loops, and automatic lead-lag pump staging.

[Result]

Soft-starting eliminated all water hammer piping shock. Pumping electrical energy consumption decreased by 34%, and automatic lead-lag cycling balanced operating hours equally across all three pumps.

// ENGINEERING SPECIFICATIONS:
PLC: Siemens S7-1200 Compact Controller
HMI: Siemens SIMATIC KTP700 Basic
DRIVE: Three 50 HP Industrial VFDs
VOLTAGE: 480V 3-Phase Distribution
Documented Project Case StudyRequest Similar System

Have a Similar Machine Project or Stoppage?

Discuss your machinery specifications directly with our automation engineers in Cincinnati.